Pinpoint Test F: B1B71:11, B1B71:15
- Refer to MANUAL CLIMATE CONTROL SYSTEM
for schematic and connector information.
Normal Operation and Fault Conditions
Evaporator Temperature Sensor, REFER to: Climate Control System - Vehicles With: Electronic Manual Temperature Control (EMTC) - System Operation and Component Description
DTC Fault Trigger Conditions
DTC Description Fault Trigger Condition HVAC B1B71:11 Evaporator Temperature Sensor: Circuit Short To Ground Module senses lower than expected voltage on the sensor feedback circuit, indicating a short to ground. HVAC B1B71:15 Evaporator Temperature Sensor: Circuit Short To Battery Or Open Module senses greater than expected voltage on the sensor feedback circuit, indicating a short to voltage or an open circuit or sensor. Possible Sources
- Wiring, terminals or connectors
- Evaporator temperature sensor
- HVAC control module
- NOTE: Use the correct probe adapter(s) when making measurements. Failure to use the correct probe adapter(s) may cause damage to the connector.
- F1 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR A SHORT TO VOLTAGE
- Ignition OFF.
- Disconnect HVAC control module C228A and C228B.
- Ignition ON.
Is any voltage present?
Yes REPAIR the circuit in question. No GO to F2 - F2 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR A SHORT TO GROUND
- Ignition OFF.
Is the resistance greater than 10, 000 ohms?
Yes GO to F3 No REPAIR the circuit in question. - F3 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR AN OPEN
- Disconnect Evaporator temperature sensor C296.
Are the resistances less than 3 ohms?
Yes GO to F4 No REPAIR the circuit in question. - F4 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR A SHORT TOGETHER
Is the resistance greater than 10, 000 ohms?
Yes INSTALL a new evaporator temperature sensor. REFER to: Evaporator Temperature Sensor CLEAR all Diagnostic Trouble Codes (DTCs). CARRY OUT the HVAC control module self-test. TEST the system for normal operation. If the concern is still present, GO to F5 No REPAIR the circuits. - F5 CHECK FOR CORRECT HVAC (HEATING, VENTILATION AND AIR CONDITIONING) CONTROL MODULE OPERATION
- Ignition OFF.
- Disconnect and inspect all HVAC control module electrical connectors (if not previously disconnected).
- Repair:
- corrosion (install new connector or terminal - clean module pins)
- damaged or bent pins - install new terminals or pins
- pushed-out pins - install new pins as necessary
- Connect all HVAC control module electrical connectors. Make sure they seat and latch correctly.
- Operate the system and determine if the concern is still present.
Is the concern still present?
Yes CHECK OASIS for any applicable service articles: TSB, GSB, SSM or FSA. If a service article exists for this concern, DISCONTINUE this test and FOLLOW the service article instructions. If no service articles address this concern, INSTALL a new HVAC control module. REFER to: Heating, Ventilation and Air Conditioning (HVAC) Control Module No The system is operating correctly at this time. The concern may have been caused by module connections. ADDRESS the root cause of any connector or pin issues.