Pinpoint Test D: B1B71:11, B1B71:15
- Refer to AUTOMATIC CLIMATE CONTROL SYSTEM
for schematic and connector information.
Normal Operation and Fault Conditions
Evaporator Temperature Sensor, REFER to: Climate Control System - Vehicles With: Dual Automatic Temperature Control (DATC)/Electronic Automatic Temperature Control (EATC) - System Operation and Component Description .
DTC Fault Trigger Conditions
DTC Description Fault Trigger Condition HVAC B1B71:11 Evaporator Temperature Sensor: Circuit Short To Ground Module senses lower than expected voltage on the sensor feedback circuit, indicating a short to ground. HVAC B1B71:15 Evaporator Temperature Sensor: Circuit Short To Battery Or Open Module senses greater than expected voltage on the sensor feedback circuit, indicating a short to voltage or an open circuit or sensor. Possible Sources
- Wiring, terminals or connectors
- Evaporator temperature sensor
- HVAC control module
NOTE: Use the correct probe adapter(s) when making measurements. Failure to use the correct probe adapter(s) may cause damage to the connector. - D1 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR A SHORT TO VOLTAGE
- Ignition OFF.
- Disconnect HVAC control module C288A.
- Ignition ON.
Is any voltage present?
Yes REPAIR the circuit in question. No GO to D2 - D2 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR A SHORT TO GROUND
- Ignition OFF.
Is the resistance greater than 10, 000 ohms?
Yes GO to D3 No REPAIR the circuit in question. - D3 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR AN OPEN
- Disconnect Evaporator temperature sensor C296 .
Are the resistances less than 3 ohms?
Yes GO to D4 No REPAIR the circuit in question. - D4 CHECK THE EVAPORATOR TEMPERATURE SENSOR CIRCUITS FOR A SHORT TOGETHER
Is the resistance greater than 10, 000 ohms?
Yes INSTALL a new evaporator temperature sensor. REFER to: Evaporator Temperature Sensor . CLEAR all Diagnostic Trouble Codes (DTCs). CARRY OUT the HVAC control module self-test. TEST the system for normal operation. If the concern is still present, GO to D5 No REPAIR the circuits. - D5 CHECK FOR CORRECT HVAC (HEATING, VENTILATION AND AIR CONDITIONING) CONTROL MODULE OPERATION
- Ignition OFF.
- Disconnect and inspect all HVAC control module electrical connectors (if not previously disconnected).
- Repair:
- corrosion (install new connector or terminal - clean module pins)
- damaged or bent pins - install new terminals or pins
- pushed-out pins - install new pins as necessary
- Connect all HVAC control module electrical connectors. Make sure they seat and latch correctly.
- Operate the system and determine if the concern is still present.
Is the concern still present?
Yes CHECK OASIS for any applicable service articles: TSB, GSB, SSM or FSA. If a service article exists for this concern, DISCONTINUE this test and FOLLOW the service article instructions. If no service articles address this concern, INSTALL a new HVAC control module. REFER to: Heating, Ventilation and Air Conditioning (HVAC) Control Module . No The system is operating correctly at this time. The concern may have been caused by module connections. ADDRESS the root cause of any connector or pin issues.