OVERRIDE Test Function
Upon selecting an OVERRIDE test function, current operation will be represented as a percentage of its full range, this value will be displayed on ECC control panel. Display will alternate between "--" and what it normally should be. Alternating display is a reminder that function is not currently being overridden. Pressing WARMER or COOLER buttons begins override at which time display will no longer alternate. Pressing WARMER button increases value while pressing COOLER button decreases value. In this way it is possible to see what effect changing this value will have, and thereby suspect systems can be checked. Normal system control can be achieved in the following 3 ways:
- Selection of another override test will cancel current override.
- Selection of another system will cancel current override.
- Overriding value beyond either extreme (zero or 99) will display "--" momentarily, and then jump to opposite extreme. If button is released while "--" is displayed, normal program control will resume.
- BS00 - TEST DISPLAY
This test will display NONE as no overrides are active at this point. - BS06 - GENERATOR DISABLE
Generator disable override will control to zero (generator ON) or 99 (generator disabled), as long as button is held. Normal control will resume upon release of buttons.